Can louvers be installed in fire rated transom frames?
Resolution:
NO - Louvers are not approved for installation in a fire rated transom / side panel frames. NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...:
Is there a fire rated version of the 33A/35A rim device?
Resolution:
There is not a fire rated version of the Von Duprin 33A/35A rim device. Only the vertical rod devices (33/3527A-F, 33/3547A-F, 33/3548A-F) can be fire rated.:
What is the maximum door size for UL fire rated doors?
Resolution:
Maximum UL Fire Rated door sizes are as follows:A-Series:4' 0" X 8' 0" single door8' 0" X 8' 0” double door or pairsB-Series4' 0" X 10' 0" single door8' 0" X 10' 0” double door or pairsCE-Series:3'...:
What is the maximum door size for ITS/WHI fire rated doors?
Resolution:
ITS/WHI is "Warnoch Hersey". ITS/WHI is the formal designation for Intertek Testing Services / Warnock Hersey. ITS/WHI is an independent agency with testing, listing, in-plant inspection, and label...:
Can I use the 990 DT trim with a fire rated device?
Resolution:
The 990DT trims are not recommended on fire rated openings. Since you cannot dog the device and the device is not electrified you are inviting people to pull on a door that will not open and possib...:
Is the Von Duprin Guard-X exit device fire rated?
Resolution:
The Von Duprin Guard-X exit device is not fire rated because the deadbolt is not spring loaded. Therefore, there would be no positive latching as required on a fire rated opening. :
What is ASTM E-119?
Resolution:
ASTM E-119 is a test standard for walls, partitions and floor or roof systems: This test standard is also used for ceramic type glasses when used as window wall and/or borrowed light frames.As...:
Are Steelcraft doors and/or frames fire rated?
Resolution:
Yes, Steelcraft doors and/or frames are available and can carry a UL, WH or FM label. The type of fire label (UL, WH or FM) is dictated by the specifications and local building code. Doors ...: