STRIKE FOR INACTIVE LEAF
”
RELATED FAQS
Question
Answer
Locknetics Electric Strikes on Double Door Applications
Resolution:
It is possible to do, but not advised or supported. The door thickness would have to be enough to accommodate the strike body, then power ran to the strike with an EPT, electri...:
What electric strike can be used on a pair of doors with an L9000 lock?
Resolution:
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.:
My COR is not allowing my inactive leaf with push side overlapping astragal to close first.
Resolution:
Astragal must be applied to pull side of active leaf, since placing the stragal on the inside of the inactive leaf will interfere with the active door closing.:
Can I use an electrified mortise with a door position switch (DPS) on a double door where dummy trim is installed on the inactive door?
Resolution:
Dummy mortise trim without a lock case (L0170/L0712) is used on an inactive door. You can use an electrified mortise with a door position switch on the active door. The strike prep must be co...:
What strike is used for in-active leaf on pair of doors with 19-R?
Resolution:
The 571 strike is used on the in-active door leaf of a pair or on the 19-V door leaf when both doors are active per template.:
What strike do I use with a Von Duprin rim device on a pair of doors with flush bolts?
Resolution:
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts. This may NOT be used on Fire Rated openings.:
What strike is required when using the 2670 Guard-X on a pair of doors?
Resolution:
With a mullion: Use the standard strike 267 With no mullion and inactive leaf being held closed with flush or surface bolts: Use the 2609 double door strike :
What strike would be used for a 25-R for pair without mullion?
Resolution:
For non fire rated doors only the 1609 strike would be used on the inactive leaf that is flush/surface bolted or with a *surface or concealed vertical rod device on other door leaf.:
What is the standard gap between a pair of doors hung with continuous hinges?
Resolution:
The standard gap between a pair of doors will be 3/16" when used with a Steelcraft "Z" astragal. If a wide inactive leaf is requested (no astragal) the gap between the doors will be...: