standard hardware locations for steelcraft for rim exit

RELATED FAQS

Question
Answer
The use of Panic Hardware and/or Fire Exit Hardware is required by the International Building Code (IBC) and NFPA 101 – The Life Safety Code, depending on which code and which edition of the code i...
Hinge Spacing: All 4 1/2" and 5" butt hinge spacing 1. Opening heights 3'0" through 4'11 15/16" (one pair butt hinges) from under head CL 9 3/4" (top of door 9 5/8") from bottom of frame ...
Hinge Backset: On the frame = 5/16" On the door = 1/4"
Lock Spacing: All standard bored locks ANSI 115.2 (161, 61L type), for mortise lock ANSI 115.1 (86 type) all locations must be altered 3/8" lower, and standard strike (ASA type). 1. Opening ...
Steelcraft locates all butt hinges from the top of the door to the centerline of each hinge as standard practice: Locating hinges to the center line of the hinge keeps all hinge locations the sa...
EPT installation guidelines are as follows: Recommended location is 6" below top hinge per template Steelcraft will locate the power transfer prep at the Von Duprin recommended template locati...
The location to the top of hinge will vary depending on hinge size used. 6'8" Frame with 1 1/2 pair of hinges (top to top): For 4 1/2" hinges from the head to top of each hinge is 7 1/2", 37 7...
All 3 hour fire rated pairs of doors do require an astragal when used without a removable hardware mullion. Pairs of doors with removable hardware mullions are treated and listed as 2 single doors...
To convert the Von Duprin 98/99 Rim or Vertical (Rod or Cable) Exit Device with functional lever (996L-R/V) to act like a rigid lever (996L-NL-R/V) with key over ride follow these steps: R...