SS signal switch

RELATED FAQS

Question
Answer
DS
The SUS can change the logic polarity of the AD400/WRI400 PIM400-TD2 outputs RTX, DPS, TROUBLE, and REN from LOCK/DOOR PROPERTIES Edit tab. You can change High to Low to High using the ed...
  These SUS settings have no effect when the AD400 is linked to a PIM400-485; because the PIM400-485 reports the logic status with RSI-485 commands and not logic levels. The settings are gray...
ALWAYS put the PIM400 in LINK mode first. On a PIM400-TD2 press the LINK1 Button for door one, and LINK2 button for door 2. With a PIM400-485 you must use the SUS/HHD to select which door to LINK.  
1. To put the AD400 in LINK mode, hold down the RTE (Lever or crash bar see below) and press the # key on the key board, or present a card to the reader.            Why press the # key? Because t...
2. AD400 requires a Request To Exit (RTX) signal to link - see the user guide instructions for the linking process.  For an AD400 to enter link mode, it must see the RTX (Request To Exit) switc...
   3. Check the AA battery level, if the AA batteries are below 4.7 volts the AD400 can fail to LINK.             Install fresh batteries, with a level of 6.0 volts or better.  
4. PIM400/AD400 COM400 plug could be damaged! The small pins in the Main PCB board connection for the RF COMM board can get bent during installation of the RF COM400 board. If the PINs are bent a...
The RX switch is required to activate the ALK. The RX switch monitors the pushbar and will signal the ALK to go into alarm when the pushbar is depressed. The RX switch also allows free in...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
Depends on what is being ordered; SS can stand for either the "Signal Switch" or the "Silk Screen" push bar. The SS (Signal Switch) and ALK (Exit Alarm) sit in the same location in the exit devi...
The AE option is now called RX (Request to Exit) to match other Allegion exit brands nomenclature. The feature of getting a signal from the pushing of the device's pushpad is the same.
The RX monitors the push bar while the LX monitors the latch bolt of the exit device. A SS device has an LX and a key cylinder switch plus an emergency push bar signage.
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
The signal switch(S) will automatically be installed in an EL1490 and EL1590 devices when built at factory. Red, Green, and Black are the wires to the switch and are shown in the 1490 instructio...
One of the following items may cause the EL1690 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
SS
There are three main failures with an ALK.  Problems are usually caused by a bad power source(battery), bad RX/LX Switch or a bad circuit board.  Try installing a new battery and wai...
SS, LX, RX