Solid red led on chexit

RELATED FAQS

Question
Answer
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
Improper mechanical adjustment or QEL calibration could cause the QEL cycle three times with solid LED and not work. First check mechanical adjustment on vertical rods or mortise lock device and co...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply.  You must use the Von Duprin PS873 or newer PS914 supply.   Related soluti...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
To program the 8310-865 receiver: Set the dip switches 1 to the "OFF" (pulse) position. Set the dip switches 2 to the "OFF" (0.5s) position. Momentarily press the " No Delay" or "Delay" ...