Solenoid pulls and releases

RELATED FAQS

Question
Answer
(For best viewing, use Chrome or Firefox browser.)ALLEGION EL SOLENOID ELECTRIC LATCH RETRACTION TROUBLESHOOTING GUIDE IF DEVICE LATCH IS NOT RETRACTING PROPERLY WHEN POWERED, FOLLOW THESE STEPS I...
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment.  You must lengthen the rod by turning the hex nut in front of the plun...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
Following could cause the EL device to pull and drop repeatedly.  Short to ground  on EL wiring.  Incorrect wire gauge used.  For wire run and gauge requirements, click HERE  Wrong power suppl...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...