sms does not detect Computer Interface Peripheral

RELATED FAQS

Question
Answer
-         With the CIP NOT inserted and the Schlage Utility Software (SUS) running o   Enter the Master Programming PIN or Present Loc...
Some Access Control Panels are designed with “Supervised” or “Dry contact” requirements for the inputs and have no common ground between the ACP (Access Control Panel) and device at the door. “S...
Schlage offers the “RLBD” to support these supervised or dry contact interface applications. The "RLBD" plugs directly into the PIM400-TD2 or PIB300-TD2 for easy hook-up.  
Please reference this Tehnical Note RLBD SES-20120418 for RLBD setup, use information, hook-up diagrams and some testing suggestions when connecting to a Supervised dry contact Access Contro...
This is a link to the RLBD Installation Instructions.
This RLBD data sheet can also be found at Schlage/Technical Support. RLBD DataSheet