Can a magnet, or sentronic device, be released and close the door from a button at a desk?
Resolution:
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiri...:
SENTRONIC
Resolution:
General term for the fire/life safety products offered by LCN.:
How many Von Duprin ALK's can be powered off a PS900 series power supply?
Resolution:
The Von Duprin exit alarm ALK draws about .25 amp. PS902 power supply powers up to 8 exit alarm ALK. PS904/914 powers up to 16 exit alarm ALK. PS906 powers up to 24 exit alarm ALK. :
Can you operate a Doromatic EL 1490 with an LCN power supply?
Resolution:
This is not possible. Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.:
When would you use the 900-4R option board in a 900 series power supply?
Resolution:
The 900-4R is used with PS900 series power supplies. The 900-4R has four independent outputs and inputs with no time delay. You can use any of these outputs with electrified hardware including EL...:
Is there a wiring diagram for EL and Von Duprin PS914-2RS power supply?
Resolution:
Reference The 914 Installation instructions.:
If using the alarm kit-ALK with the 99 device what power supply is needed?
Resolution:
Exit alarm ALK operates with 9VDC battery and doesn't required a power supply.If you choose to hard wire the exit alarm ALK use the PS902 power supply.Exit alarm ALK requires 24VDC regulated power ...: