senior swing operator Hold open
”
RELATED FAQS
Question
Answer
What would cause a Senior Swing to open too far?
Resolution:
The Senior Swing operator is designed to power open the door to 90°. The built in dead stop (in the gearbox) prevents it from opening any further. If the Senior Swing operator is opening to far (pa...:
What would cause a Senior Swing to open only 10 degrees and then close?
Resolution:
Issue/Symptom – upon receiving an activation input the Sr Swing gearbox opens only about 10 degrees and then returns to the close position. Unit will never learn opening nor function pro...:
What causes a Senior Swing door to hang open and not close?
Resolution:
First, turn off the power to the Senior Swing. If the door closes, check controller for a constant activation signal from an activation device. If door continues to hang up and will not close...:
What is a Senior Swing 9540 RF?
Resolution:
The Senior Swing Series used to have a 2 gearbox options, a "standard force" (15 lbs) and a "RF - reduced force" (11 lbs). In November 2009 RF option was eliminated and we made the standard gearbox...:
When did we start shipping the Senior Swing, Benchmark, and Falcon operators with the ES Filter?
Resolution:
On the Benchmark, if there is line noise from a strike then the unit will lose it's hold open time. Adding the ES Filter, which is a diode, will resolve this issue and the unit will hold it's...: