Question
Answer
What do I need to use a fire alarm board with a PS914?
Resolution:
The Basic PS914 power supply will not accept a 900-FA fire alarm board. 900-8F option board is required with PS914 power supply to accept 900-FA fire alarm board (900-8F is an adaptor board for...:
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
How do you get a 4600 Series operator out of "Fire Alarm" mode?
Resolution:
The "Fire Alarm" indication occurs when there is no connection across terminals 13 & 14. Check to verify that the "Fire Alarm" shunt (R1 jumper) on the I/O board has not been cut. Install jumpe...:
FIRE ALARM
Resolution:
FA:
Can you manually pull a 4040SE out of hold open?
Resolution:
The holding force on an SE/ME Series door closer is approximately 35 lbs. and they can be manually pulled out of hold open with approximately 35 lbs of force. :
What will cause no output of 24V on the 900-2RS?
Resolution:
Checking the following items: The setting of the PS914 is set on 24VDC You measure 24VDC from the PS914 mother board The 900-2RS is plugged into the PS914 power power supply Either the fire a...: