ASTM E-119 is a test standard for walls, partitions and floor or roof systems:
This test standard is also used for ceramic type glasses when used as window wall and/or borrowed light frames.
...
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...
Elevation frames are available in:
F-Series (F16 or F14)
FN-Series (FN16 or FN14)
MU-Series (MU16, MU14)
Additional parameters of the frame components:
Perimeter (Head and Jambs) Frame:
...
NO - Louvers are not approved for installation in a fire rated transom / side panel frames.
NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...
No. Fire rated double egress frames must be a stand alone 3 sided frame assembly.
If transom lights and/or sidelights are required, they must be built and installed as separate Fire Window assemb...