POWER SUPPLY REQUIRED FOR CHEXIT

RELATED FAQS

Question
Answer
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
Following information determine number of the Chexit devices that were shipped prior to 8-24-2015 from the factory with solenoid driven can be hooked up to a single Von Duprin PS873 or PS914 p...
The following could cause the fuse to blow in the power supply with devices shipped prior to 8-24-2015 with solenoid driven when Chexit device is arming. Wrong power supply Confirm PS873 or...
The following are needed for a basic installation: Fire alarm contact is always required with Von Duprin Chexit device. 1 1/4" Mortise cylinder with straight cam is required to turn&n...
Chexit devices shipped after 8-24-2015 with motor driven: The Chexit device will use a 1 1/4" mortise cylinder with straight cam. Schlage cylinder 20-001-114 recommended. CAUTION: The length of t...
Chexit devices shipped prior to 8-24-2015:The CX device will need a 1 1/4" mortise cylinder with a straight cam per page 2 of the installation instructions. A 996L-M for a 1 3/4...
Depends on which options are used on the Chexit device. Most application use 6-8 wires, but can use up to ten wires.
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...