power supply for electrified strike

RELATED FAQS

Question
Answer
The PS861 will not power an EL device.  The high 16Amp current of the EL requires the PS914-2RS, PS914-4RL or the older PS873-2 power supply to operate.
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or&n...
The capabilities of the auto operator and the required operation of the opening will affect the selection of a power supply.
The 900-4RL has two out put for EL devices and signals to the auto operators to open the doors. PS914 power supply is required with 900-4RL option board to operate the EL device and auto operato...
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
Applies to L9090EL/EU, L9091EL/EU, L9092EL/EU, L9093EL/EU, L9094EL/EU, L9095EL/EUThese models require 12/24 VDC with a peak current of 0.4 amps.  The following po...
Applies to L9080EL/EU, L9082EL/EU (Discontinued)The Schlage L9080 EU/EL and L9082 EU/EL require 24 VAC/VDC with a peak current of 1.3 Amps at 5 to 10 second intervals and a holding curren...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into a standard 4 ...
Follow the steps below to troubleshoot the problem. Measure the voltage at the electric strike. If the strike is FSE and not locking there should be no voltage at the strike and if it is FS there ...