Question
Answer
Can a Von Duprin delay egress controller DE5101 run a pair of doors?
Resolution:
One Delayed Egress Controller (DE5101) can run two mag locks on a pair of doors, provided the doors are not controlled independently:
Can we run both mag locks and EL devices from the PS 914?
Resolution:
It requires 900-4RL and 900-FA option boards to release the mag locks when a fire alarm is activated. Specify PS914 x 900-4RL x 900-FA.:
Where is the cross reference list for PS800 to PS900 series power supplies?
Resolution:
Von Duprin PS914-4RL power supply replaces the PS873-4TD.:
How many Von Duprin QEL devices can be connected to a power supply?
Resolution:
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...:
Can you power a electric strike from the 7900 control boxes?
Resolution:
The power supply output in the 7900 series control box is a 12VDC output, rated at (1/4A) 0.250A. It cannot be used to power a strike or maglock. You need to have a separate power supply for the st...: