Following could cause the fuse to blow in Von Duprin PS873 power supply.
PS873 power supply provides 2AMP at 24VDC or 4AMP at 12VDC. If this limit is exceeded the fuse will blow in the power sup...
The following could cause the fuse to blow in the power supply with devices shipped prior to 8-24-2015 with solenoid driven when Chexit device is arming.
Wrong power supply Confirm PS873 or...
If the Main AC fuse is blowing, the control box is defective and needs to be replaced. The "Main Fuse" is a (5x20MM) 1 Amp Slow Blow fuse.
If the 12VAC fuse is blowing, verify they are not trying...
The old MPB842 power supply will power up to two EL electric panic bars but will not power the QEL devices.
A defective potted module inside the electric panic bar or defective power supply coul...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light.
Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm.
Mechanical adjustment such as vertical rods. Disconnect t...
The following could
cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to
go into weak alarm with solid LED light:
Wrong power supply- Chexit
device requires a...