Power on, motor not running

RELATED FAQS

Question
Answer
A 4600 (4630/4640) not opening to a full 90 degrees could be caused by a couple things: The Opening Force could be set too low. Try increasing the opening force adjustment on the controller a 1/...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into a standard 4 ...
The following items may cause the  PS900 series power supply to have no DC output voltage. 1. If  the DC voltage selection jumper is missing, the power supply will not provide any D...
Following could cause the 900-2RS board not to operate: If 900-2RS board is not plugged into the PS914 mother board. If PS914 power supply is selected for 12VDC instead of 24VDC. If control co...
  The super capacitor powers the AD300 motor to the correct power fail position, secure or unsecure, during a power fail event. When power is restored to an AD300 in the Power Fail secure ...
  Recognize the AD300 when first powered, or when recovering from a power loss, may NOT be fully functional for two minutes until the AD300 super capacitor is fully recharged. During this rec...