MODIFYING RATED FRAMES FILLER FOR ELECTRIC STRIKE?

RELATED FAQS

Question
Answer
Yes, a filler plate can be used to cover an EPT prep as long as it is made from the same material as the frame. This information can also be found in NFPA 80 under Chapter 5 for Field Modifications.
Order the 4854 mullion 'BLANK' x size x finish
The following application information apply to the 5100 electric strike: Can only be used on a single door with a cylindrical lock Can not be used on a pair of doors Can not be used on a mullion
Von Duprin doesn't offer any electric strike to fit into 1 1/2" aluminum/metal faced frame.  Minimum requirement to install 6211/6211AL is 1 15/32" mortise depth.
Aluminum mullions 5654 or 5754 are not designed to accept any electric strike including 6300 surface mounted electric strike.
There is not enough room to install two 6111 electric strikes back to back in 4854 mullion.
The 6216 electric strike was designed only for use with only the Folger Adams 310-3-1 mortise lock with deadbolt. The dead bolt must be retracted manually for the the strike to operate.