LX RX with QEL
”
RELATED FAQS
Question
Answer
What are the Von Duprin part numbers for RX, LX and RX,LX-LC switch kits for field installation?
Resolution:
The attached table shows the part numbers for LX-RX and LX-RX-LC switches field installed.:
Can QEL and RX be added to an existing 9927?
Resolution:
The QEL conversion kit (3' or 4') and the RX switch kit (050251-00) can convert the 9927 to QEL-RX9927 device.:
Can the Von Duprin exit alarm ALK and electric latch retraction QEL or EL device be in the same device?
Resolution:
No, Von Duprin exit alarm ALK and electric latch retraction QEL or EL are installed in the same location and can't be ordered together with the same device.:
What power supply is used with RX or LX switches?
Resolution:
The RX switch is request exit and the LX switch is latch bolt monitor switch. They do not require a power supply directly. The electrified hardware that the RX or LX switch...:
Can a pneumatic (PN) 33A/35A/98/99 exit device use the RX or LX switches?
Resolution:
PN33/35/98/99 Pneumatic exit devices are not usually used with RX or LX switches since the Pneumatic PN device is used instead EL to eliminate the electric from the device.:
Is it possible to have EL/QEL and an exit alarm on the same device?
Resolution:
It is not possible for an exit device to have an EL/QEL component and an exit alarm. There is not enough room in the device to house both items.:
Can you convert the EL33A/35A or EL98/99 series exit device to the QEL device?
Resolution:
The Von Duprin EL33A/35A/98/99 device can be converted to the QEL device by getting the correct sized QEL baseplate conversion kit. The existing PS914 or PS873 power supply can be used. ...:
Is there a template that shows where to drill the hole for E/EL/SS/RX/LX/CX wires?
Resolution:
The hole should be drilled in the field once the end cap is located on the door. It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...:
What is the difference between Von Duprin LX and/or RX switches and the Signal Switch SS option?
Resolution:
The RX monitors the push bar while the LX monitors the latch bolt of the exit device. A SS device has an LX and a key cylinder switch plus an emergency push bar signage.:
Can you add the LX option to a Von Duprin device that already has the RX option?
Resolution:
The Von Duprin RXLX combination switch must be ordered together as one assembly. Existing RX or LX switch must be removed to install the combination RX LX switch. Make sure correct RX LX combinatio...: