Why does the AD300-993 and AD400-993 require Von Duprin RX-LC switch
Resolution:
Here is detailed information on why the Von Duprin RX-LC Swtich is required by the AD300 and AD400 993 units. A low current switch is needed because … - &nb...:
What is the difference between an RX switch and an RX-LC (low current) switch?
Resolution:
The standard Von Duprin switches (RX and LX switches in exit devices, and DS dual switches in 6100 and 6200 Electric Strikes) are rated for 0.05A to 2A @ 24 VDC. The low curren...:
What drains the AA batteries on an CO-Series lock?
Resolution:
Causes for AA battery drain in CO-Series LOCKS - Possible Cause Fix/Corrective Actions One of the four AA batteries was inserted reversed and the reserved battery drains the other batteries. ...:
What current should an AD-Series or CO-Series lockset draw while in its low power "Sleep" mode?
Resolution:
Use a multi-meter in series with the batteries to measure battery current. Be sure your multi-meter can accurately measure very low current, in the micro-amp range. See the attached Technical Not...:
What drains the AA batteries on an AD-Series lock?
Resolution:
Causes for AA battery drain in AD-Series LOCKS Possible Cause Fix/Corrective Action 1) One the four (or eight) AA was inserted reversed and the rese...: