LCN Operator power requirements

RELATED FAQS

Question
Answer
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...
The capabilities of the auto operator and the required operation of the opening will affect the selection of a power supply.
The 900-4RL has two out put for EL devices and signals to the auto operators to open the doors. PS914 power supply is required with 900-4RL option board to operate the EL device and auto operato...
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.
LCN does not does not have or supply any information for the old (obsolete) "High Energy" Dor-O-Matic Sliding doors, Bi-Fold doors or Astro Swing doors. You MUST be AAADM certified to work on, or g...
The 4600 series operator requires a 120 VAC @ 1.5 Amp power input to be field connected. Hardwiring is always recommended, but a "plug-in" line cord can be installed (by others) with the proper cor...
This is not possible.  Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.
The Senior Swing (2800/9500) Series operator has a 120VAC @ 2.5 Amp current draw for a single door (2811/9531/9542) or simultaneous pair(2853/9553). The independent pair units (2863/9563) have a 12...