All Schlage/XceedID wiegand proximity readers currently understand:
-ASK (Amplitude Shift Key) - Used in GE/CASI
-FSK (Frequency Shift Key) - Used in HID Prox, AWID, and Lenel
The third proximit...
ISOX card technology is no longer supported - contact XceedID sales
ALWAYS put the PIM400 in LINK mode first. On a PIM400-TD2 press the LINK1 Button for door one, and LINK2 button for door 2. With a PIM400-485 you must use the SUS/HHD to select which door to...
1. To put the AD400 in LINK mode, hold down the RTE (Lever or crash bar see below) and press the # key on the key board, or present a card to the reader.
...
2. AD400 requires a Request To Exit (RTX) signal to link - see the user guide instructions for the linking process.
For an AD400 to enter link mode, it must see the RTX...
3. Check the AA battery level, if the AA batteries are below 4.7 volts the AD400 can fail to LINK.
Ins...
4. PIM400/AD400 COM400 plug could be damaged!
The small pins in the Main PCB board connection for the RF COMM board can get bent during installation of the RF COM400 board. If the PINs are be...
Information on low battery threshold and nuisance delay is noted below: New firmware now has improved levels.
- These are approximate values/levels which change with measurement meters and measure...
AD400/AD200/AD250 After ADFwPkg 2.17.0 - June 2011
4 Battery Holder
New batteries = 6.2 VDC
Low battery threshold is 4.7 VDC for SM & MT - and 3.7 VDC for MAG and PROX (USB stops working at 4...
AD400/AD200/AD250 After ADFwPkg 2.17.0 - June 2011
8 Battery Holder
New batteries = 12.4 VDC
Low battery threshold is 7.2 VDC
Critical battery threshold is 6.9 VDC
Coin cell = new/...
CO2004 Battery Holder (ONLY)
New batteries = 6.2 VDC
Low battery threshold is 4.2 VDC
Critical battery threshold is 3.9 VDC
Coin cell = new/full is 3.0 VDC, low is 2.8 VDC
CO2504 Battery Holder (ONLY)
New batteries = 6.2 VDC
Low battery threshold is 4.2 VDC
Critical battery threshold is 3.9 VDC
Coin cell = new/full is 3.0 VDC, low is 2.8 VDC
CO200 & CO250 Disable coin cell Nuisance delay and blink,
With CO.A.7 and SUS 4.10.2 or newer for CO200 and CO250, you can use the SUS/HHD, under Lock Properties, Edit, to de-select, DISABLE, t...
No, the 33A is not compatible with the AD and CO 993 chassis units. The 33A can only be driven in a clockwise direction. This would restrict it to right hand installs only.
A design change occurred in 2001 to address a locking/unlocking issue with the discontinued D73 lever locks. This included modifying the cam and plug, spindle and using a different plung...
Dynamic Channel Switching is a feature of the Schlage AD-series wireless access point modules. Dynamic Channel Switching (DCS) increases the robustness of the wireless RF communication in a noisy r...
Here is a Technical Note on what Dynamic Channel Switching is, what it improves, how to set-up, and frequently asked DCS questions. DCS Tech Note here
Setting Dynamic Channel Switching 1) Connect and couple the SUS to the PIM400 you intend to change. See the SUS User Guide for details 2) Under “PIM Properties” and the “Edit” tab is ...
This change was implemented in firmware package CO.A.6 (or later) to help the customer in the communication and coupling process between the CO200 (CO250) and the hand held device (HHD). ...
The green LED is to be lit up until the spindle (Triangles and Key Switch) are aligned properly; providing a visual indication of the problem.
If the mechanical alignment of the triangles on the back of the outside escutcheon are not aligned, the CO200 or CO250 will not connect with the SUS/HHD and will appear to be unresponsive...
In firmware CO.A.6 (or later) the Schlage button on the CO200 (CO250) will turn green anytime that the spindle triangles on the front escutcheon are out of alignment or the mechanical key switch is...
When unlocking the CO200 door by mechanical key override, the green led will be continuously ON until the key is released. This will occur after firmware CO.A.6 (or later) has been installed int...
The process to change the Credential Reader on an AD-Series lock is as follows:
Note: To ensure firmware compatibility of the lock and reader, it is important that the firmware in the LOCK and the...
The Schlage full size interchangeable core (FSIC) prepped B560F, B561F, and B563F deadbolts all require a UL fire cup (R) in order to be UL listed. This fire cup is s...
The minimum door thickness that the AD or CO series lock will mount on is 1 3/8". Be advised that this will require additional spacers to be ordered separately to allow the lock to mount...
The indicator on a cylindrical hotel lock is a small pin that projects outward from the face of the cylinder plug (Figure 1) when the inside push button is depressed. When this pin is ...