Question
Answer
What is the part number for the EAK PCB only for Monarch Falcon devices?
Resolution:
This circuit board will NOT work on the updated 24/25 Alarm Kits that released June 11th, 2012.:
What is the current draw of a Von Duprin exit alarm kit ALK?
Resolution:
The current draw of a Von Duprin exit alarm ALK is .25 amp when alarm is activated.:
If using the alarm kit-ALK with the 99 device what power supply is needed?
Resolution:
Exit alarm ALK operates with 9VDC battery and doesn't required a power supply.If you choose to hard wire the exit alarm ALK use the PS902 power supply.Exit alarm ALK requires 24VDC regulated power ...:
Is there an Exit Alarm Retrofit Kit (EAK) for the 19 series?
Resolution:
These kits for the 19 Series were discontinued June 11th, 2012 when the updated alarm kit for the 24/25 series was released. Prior to discontinuation, it was o...:
Will one PS902 power supply run two Von Duprin exit alarm ALK'S?
Resolution:
PS902:
What could cause the Von Duprin exit alarm ALK to turn off after one or two minutes?
Resolution:
If the spring on the Von Duprin exit alarm ALK board is not located correctly as shown on the instructions, then the vibration from the horn allows the cylinder to turn and shut the exit alarm ALK ...:
What is the part number for the ALK sign?
Resolution:
The sign for exit alarm, ALK, is SIGN-1.:
What power supply replaces the Von Duprin 9VDC PS9 power supply?
Resolution:
The PS9 power supply was discontinued. The new exit alarm ALK can either use a 9VDC battery or 24VDC regulated power supply. There is no direct replacement for Von Duprin PS9 power supply. Cur...: