hospital stop lead lined frame

RELATED FAQS

Question
Answer
Lead lined frames are intended for use in the X-ray Room locations in Health Care facilities. Frames are provided by Steelcraft prepped as follows:  Frames are supplied knock-down (KD). Fram...
Hospital Stops are located at the bottom of the frame jambs and/or mullions. The integral door stops are terminates above floor line and is closed with a 45° or 90° angle to facilitate cleaning at ...
Yes, hospital stops are available on fire rated frames. Maximum approval = 3 hour Maximum sizes:  singles up to 4'0" x 8'0" pairs up to 8'0" x 8'0" Maximum hospital stop height 6" from bot...
Radiation, Lead Lined
The determination was made that Lead Lined covers are no longer needed for the LCN product line, see below Marketing/EHS document. Lead Lined cover discontinuation letter
The door template L1 states: "Lead Lining: When L9000-Series or L400-Series locks are ordered with lead lining, add 1/8" to the width of the mortise cut-out on the lock case cover side of installa...
Lead lining is not needed, since the channel or through bolt is solid and the x-rays will not penetrate the solid metal.
Not specifically for lead lined doors.  But the standard hinges should work and not hit the lead lining in the door.  Since standard lead layers vary, check with door manufacturer an...