hospital stop lead lined frame

RELATED FAQS

Question
Answer
Lead lined frames are intended for use in the X-ray Room locations in Health Care facilities. Frames are provided by Steelcraft prepped as follows:  Frames are supplied knock-down (KD). Fram...
Hospital Stops are located at the bottom of the frame jambs and/or mullions. The integral door stops are terminates above floor line and is closed with a 45° or 90° angle to facilitate cleaning at ...
Yes, hospital stops are available on fire rated frames. Maximum approval = 3 hour Maximum sizes:  singles up to 4'0" x 8'0" pairs up to 8'0" x 8'0" Maximum hospital stop height 6" from bot...
Radiation, Lead Lined
The determination was made that Lead Lined covers are no longer needed for the LCN product line, see below Marketing/EHS document. Lead Lined cover discontinuation letter
The door template L1 states: "Lead Lining: When L9000-Series or L400-Series locks are ordered with lead lining, add 1/8" to the width of the mortise cut-out on the lock case cover side of installa...
Lead lining is not needed, since the channel or through bolt is solid and the x-rays will not penetrate the solid metal.
Ives does not offer a continuous hinge designed specifically for lead lined doors.  Standard hinges may work if the hinge and mounting hardware do not penetrate the lead lining in the door.&nb...