Question
Answer
Can a magnet, or sentronic device, be released and close the door from a button at a desk?
Resolution:
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiri...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
What could cause the Von Duprin EL solenoid not to hold when mechanism cover plate is slide over the solenoid?
Resolution:
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment. You must lengthen the rod by turning the hex nut in front of the plun...:
Can you manually pull a 4040SE out of hold open?
Resolution:
The holding force on an SE/ME Series door closer is approximately 35 lbs. and they can be manually pulled out of hold open with approximately 35 lbs of force. :
In what direction should the hold open nut be pointing for a 4041 H closer, up or down?
Resolution:
Make sure that the hold open nut is not on upside down. The orientation of the hold open nut depends on the mounting. On a Top Jamb "Push Side" mount, the hold open nut would poi...:
What would cause a 4111 HEDA to not hold open?
Resolution:
The correct method (process) for setting the hold open is: The 4110 HEDA arms are handed, verify correct hand arm. (RH or LH stamped on shoe bracket) Loosen the hold open nut at shoe bracket. ...:
What do I need to do to make my 4041 Reg/PA a hold open arm?
Resolution:
When placing an order for a 4041/4040XP Rw/PA with hold open, it would be ordered as a 4041 /4040XP Hw/PA. For an existing Rw/PA requiring the addition of a hold open function, a hold open arm woul...:
Where does the hold open switch on the 4630 / 4640 wire into on the 1-24 single terminal strip?
Resolution:
The 4600 hold open switch (for the new 1-24 single terminal strip I/O board) wires into terminals 2 and 6 or 4 and 6.: