high engery operator
”
RELATED FAQS
Question
Answer
What would cause a Senior Swing to open too far?
Resolution:
The Senior Swing operator is designed to power open the door to 90°. The built in dead stop (in the gearbox) prevents it from opening any further. If the Senior Swing operator is opening to far (pa...:
How do you change a 9130 Benchmark to a 9140 Benchmark?
Resolution:
The only difference between the 9130 and 9140 Benchmark operators are the arms. To convert a Benchmark 9310 (pull) to a 9140 (push), order a 9140-3077 push arm assembly ...:
How do I get service on my Astro Swing operator that isn't working properly?
Resolution:
LCN does not does not have or supply any information for the old (obsolete) "High Energy" Dor-O-Matic Sliding doors, Bi-Fold doors or Astro Swing doors. You MUST be AAADM certified to work on, or g...:
What operator is best for high traffic automatic use.
Resolution:
The Senior Swing 9500 or 2800 series operator is designed to for "High Traffic - High Abuse" areas.:
Can a 4640 operator be mounted on a Flush Ceiling application?
Resolution:
4640 Flush Ceiling mounting requires a minimum 1-3/4" Header, and a minimum 3-3/4" Top Rail on the door.:
Can a 9100 series Benchmark be used on a high traffic exterior door?
Resolution:
The recommended application for the 9100 series Benchmark operator is low traffic exterior doors, or low/moderate traffic interior doors. The Benchmark series operator "is not" recommended for use ...:
How are actuators wired to a 7900 or 7980 series control box?
Resolution:
The "common" of all the actuator switches will connect to terminal 10. The N.O. (normally open contact) will connect to Terminal 5, 6, 7 or 8 depending on which control box is used and the function...:
What is the power output on the Senior Swing 9500 series?
Resolution:
Below information is for the 120v Sr Swing Operators.For Sr Swing digital Control Boxes made from 2006 to Dec. 9th 2019 the Senior Swing operator had a 24VAC output , rated at 1.5 Am...: