Question
Answer
What is the maximum glass size available on the T-Series door?
Resolution:
Glass lights are available in fire rated T-Series doors: Limited to one (1) light per door leaf with a maximum of 100 square inches of exposed glass. This applies to all hourly ratings a...:
Is replacement aluminum glass light trim available?
Resolution:
Aluminum trim is not available. All of our current trim offerings are steel.:
What glass light kits are available in doors?
Resolution:
Glass Light is a preparation in a door for view window, vision and/or glazing including glass stop and glazing bead and may also be refereed to as a lite.Doors are available with a wide v...:
What is the maximum glass light size on a 90 min (1 1/2 hour) fire rated door?
Resolution:
Standard listed wire glass: one (1) light with 100 in2 per door leaf max.Firelite or other appropriately listed glass:• FM maintains one (1) light with 100 in2 per door leaf max.• UL &...:
What fire ratings are available on DW-Series Borrowed Lights?
Resolution:
DW-Series Fire Rated Borrowed Lights are available in the following sizes: 60 minute (1 hour) rating = 2721 square inches of visible glass. maximum frame rabbet to rabbet dimensions = 78 1/4...:
What is the maximum glass light size available on a 20 minute sidelight frame?
Resolution:
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...:
Can a 3 hour A labeled Fire Door be prepped for multiple glass lights?
Resolution:
A fire rated door for 3 hours can have one glass light maximum: 100 square inches and must have an approved glass (Firelite type) Max glass size cannot exceed 12" in width or 33" in height. Wi...:
What is the maximum glass light size on a 3 hour (180 minute) fire rated door?
Resolution:
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...:
What is exposed glass size?
Resolution: