GBK ok for fire rated doors
”
RELATED FAQS
Question
Answer
Can Von Duprin GBK's be stacked up to clear a 9/16" glass bead on a fire door?
Resolution:
You can only use one GBK Glass Bead Kit (1/4") per device on fire rated openings. Glass Bead Kit is for use on doors with raised glass beads.:
What is the maximum glass light size on a 3 hour (180 minute) fire rated door?
Resolution:
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...:
What is the maximum glass light size on a 90 min (1 1/2 hour) fire rated door?
Resolution:
Standard listed wire glass: one (1) light with 100 in2 per door leaf max.Firelite or other appropriately listed glass:• FM maintains one (1) light with 100 in2 per door leaf max.• UL &...:
Fire Rating for AD and CO locks
Resolution:
The AD and CO locks both have a 3 hour fire door rating. Please see URL for more info. UL Fire Rating List:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
What is the max rating available on an full glass (FG) door?
Resolution:
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...:
Can 5100 electric strikebe used on fire rated door?
Resolution:
The Von Duprin 5100 electric strike is not for fire rated applications.:
Is the Von Duprin 6223 fire rated for pairs of wood doors?
Resolution:
The 6223-FSE electric strike is fire rated for pairs of wood doors, but check with wood door manufacturer to see if they have been approved for this application.: