fire rated strike

RELATED FAQS

Question
Answer
The Von Duprin 5100 electric strike is not for fire rated applications.
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts.  This may NOT be used on Fire Rated openings.
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
The 909 strike is used in single and paired non-fire rated and single fire rated openings.  The 954 strike is used in fire rated paired openings.
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.
Von Duprin 6300 electric strike will operate with 88 rim but not 88F fire rated exit devices.