fire rated exit device with overlapping astragal
”
RELATED FAQS
Question
Answer
What strike do I specify with the 9975 device on a pair of 1 3/4" thick doors with a flat overlapping astragal mounting on the exterior of the active door?
Resolution:
Use the 575-2 strike with 9975 device on a pair of 1 3/4" thick doors with overlapping astragal mounting on the exterior of the active door. The strike lip has been cut off to eliminate any interfe...:
Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...:
My COR is not allowing my inactive leaf with push side overlapping astragal to close first.
Resolution:
Astragal must be applied to pull side of active leaf, since placing the stragal on the inside of the inactive leaf will interfere with the active door closing.:
Can Steelcraft doors be prepped for the 98/9949 Concealed Vertical Cable Exit Device?
Resolution:
Yes, as an option, Steelcraft doors are available with factory prepared for the 98/9949 Concealed Vertical Cable Exit Device.L, B, CE, T and CE-Series doors are available factory preparedDoor prepa...:
Is the Von Duprin 1609 strike fire rated for pairs of doors?
Resolution:
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...:
Where do I install my Auxiliary Fire Latch (AFL) in a Less Bottom Rod, Fire Rated (LBR-F) exit device?
Resolution:
Installation should be 6" from bottom of the door. See attached templates as reference. T-5494 for HM Doors W-5494 for Wood Doors:
Can a panic device be converted to a fire-rated device in the field?
Resolution:
A standard exit device can't be modified to a fire rated exit device. In order to get a product with the UL fire label, a new device must be purchased. This is a UL requirement.:
Is there a fire rated version of the 33A/35A rim device?
Resolution:
There is not a fire rated version of the Von Duprin 33A/35A rim device. Only the vertical rod devices (33/3527A-F, 33/3547A-F, 33/3548A-F) can be fire rated.: