Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...:
When are Panic Devices required?
Resolution:
The use of Panic Hardware and/or Fire Exit Hardware is required by the International Building Code (IBC) and NFPA 101 – The Life Safety Code, depending on which code and which edition of the code i...:
How can I cover a 86 or 161 prepped door with a 19-R?
Resolution:
The 4170 cover plate can be used to cover the 86 & 161 prepped doors.:
What cores are offered for insulated doors?
Resolution:
Insulated Core Options: Steelcraft L-Series doors are available with the following 2 optional insulated cores: Polystyrene slab - this core is available in non fire rated and fire rated doors...:
Are astragals required on 3 hour rated pairs of doors?
Resolution:
All 3 hour fire rated pairs of doors do require an astragal when used without a removable hardware mullion. Pairs of doors with removable hardware mullions are treated and listed as 2 single doors...:
What is the maximum glass light size on a 3 hour (180 minute) fire rated door?
Resolution:
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...:
What is the maximum glass light size on a 90 min (1 1/2 hour) fire rated door?
Resolution:
Standard listed wire glass: one (1) light with 100 in2 per door leaf max.Firelite or other appropriately listed glass:• FM maintains one (1) light with 100 in2 per door leaf max.• UL &...:
Fire Rating for AD and CO locks
Resolution:
The AD and CO locks both have a 3 hour fire door rating. Please see URL for more info. UL Fire Rating List: