Falcon exits electric latch retraction
”
RELATED FAQS
Question
Answer
How do you test a Falcon 24 or 25 Series EL solenoid?
Resolution:
The resistance readings for a Falcon 24 or 25 Series EL solenoid should read;Green to Yellow = Pull Coil, should measure between 1 and 2 ohms of resistance. Green to Orange = Hold Coil, s...:
Can the Von Duprin EL option be added to any existing 98/99 device?
Resolution:
The Von Duprin EL option can be added to any existing 33A/35A, 98/99 series exit devices. :
Can fire rated exit devices have electric latch retraction?
Resolution:
Yes, fire rated exit devices can have electric latch retraction. However, the devices must be tied into a fire alarm system to remove power from the units so the doors will be latched in the ...:
What power supply is needed for EL devices?
Resolution:
You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board will power 1 or 2 devices that do not require timing from pow...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
Is there an EL conversion kit for the Falcon 2390 exit device?
Resolution:
There is no EL conversion kit for a 2390, the device will need to be replaced.: