falcon el gauge
”
RELATED FAQS
Question
Answer
Why is the Von Duprin PS873 power supply buzzing or chattering?
Resolution:
Some transformers in the power supplies provide a little humming noise and that is normal. If the humming in Von Duprin PS873 power supply is loud follow these steps. Remove the load from the outp...:
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
Resolution:
:
What gauge wire is needed for CX red and black power wires?
Resolution:
For Product Shipped prior to 8-24-2015 with solenoid and EPT or Door Loops: a. 0-100 ft, use #14 Gauge Wire ...:
What size wire and run is recommended when using a PS914-2RS?
Resolution:
For Product Shipped Prior to August 2012 using the old (black) potted module:a. 0-100 ft 14 gauge wireb. 0-200 ft 12 gauge wire&nbs...:
Does the wire size of an EPT affect the operation of an EL device?
Resolution:
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....:
Is there an EL conversion kit for the Falcon 2390 exit device?
Resolution:
There is no EL conversion kit for a 2390, the device will need to be replaced.: