fail-safe electric strike
”
RELATED FAQS
Question
Answer
Can the 6300 electric strike be Fail Safe?
Resolution:
The Von Duprin 6300 surface mounted electric strike is only available as Fail-Secure.:
How to convert the Von Duprin 6000 series electrical strike from Fail Secure to Fail Safe or Fail Safe to Fail Secure?
Resolution:
Part numbers: FS slider, part # 090591 (Use for all EXCEPT 6211WF/6212WF/6221/6223. See 090798 below) FS slider, part #090798 (Use this slider for FS models 6211W...:
Why won't the 5100 24v strike work on both a RH & LH door?
Resolution:
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...:
Can 24 volts be run to a 12 volt 6000 series electric strike solenoid?
Resolution:
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid. You must change to a 24V solenoid, part number 050240-00.:
Does the 9540 Senior Swing need a separate relay board for wiring to electric locks?
Resolution:
The Senior Swing control box has a built in (programmable) relay output for connection to a Fail Safe/Fail Secure electric strike/maglock or to an EL Device power supply.:
Common wiring diagrams
Resolution:
Electronic Protocols: Access Control Door with electric trim Access Control with electric strike Access control with electric strike and LCN 460...: