Can I convert an L9000 electrified lock to fail safe or fail secure?
Resolution:
Procedure for the L9080EL/EU and L9082EL/EUTo modify an electrified L9000 from EU to EL or EL to EU move the link pin to the appropriate location indicated below in Figure 1. :
How to convert the Von Duprin E996L trim from FS fail safe to FSE fail secure?
Resolution:
The E996L will ship FS fail safe from the factory if you don't tell us, You can order either FS/FSE. Can be converted to FSE fail secure. To convert the 996L to E996L (fail safe or fail secur...:
Why is the electric E996L-FSE trim used with a Chexit CX99 exit device?
Resolution:
The E996L-FSE trim is needed if the application requires fail-secure operation from the trim side of the opening. When power is out on Chexit device, E996L-FSE trim will remain locked to ...:
Can the state of the E360L be changed in the field?
Resolution:
To convert the E360L electric trim from fail safe to fail secure or vice versa you need to replace the solenoid. The 050743 is the fail secure and 050744 is the fail safe solenoid kit. ...:
Can the 6300 electric strike be Fail Safe?
Resolution:
The Von Duprin 6300 surface mounted electric strike is only available as Fail-Secure.:
How to convert the Von Duprin 6000 series electrical strike from Fail Secure to Fail Safe or Fail Safe to Fail Secure?
Resolution:
Part numbers: FS slider, part # 090591 (Use for all EXCEPT 6211WF/6212WF/6221/6223. See 090798 below) FS slider, part #090798 (Use this slider for FS models 6211W...: