electronics strike fail safe on fire alarm?
”
RELATED FAQS
Question
Answer
Common wiring diagrams
Resolution:
Electronic Protocols: Access Control Door with electric trim Access Control with electric strike Access control with electric strike and LCN 460...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
Can the 6300 electric strike be Fail Safe?
Resolution:
The Von Duprin 6300 surface mounted electric strike is only available as Fail-Secure.:
How to convert the Von Duprin 6000 series electrical strike from Fail Secure to Fail Safe or Fail Safe to Fail Secure?
Resolution:
Part numbers: FS slider, part # 090591 (Use for all EXCEPT 6211WF/6212WF/6221/6223. See 090798 below) FS slider, part #090798 (Use this slider for FS models 6211W...: