electric strike with vertical rod
”
RELATED FAQS
Question
Answer
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
Can the 283 strike be used with a metal frame with concealed vertical rod devices?
Resolution:
No, per the UL Compliance group, the concealed rod devices are only tested with the 338 strike with metal frames. This applies to panic and fire applications. The 283 strike may only be used ...:
Can the Von Duprin 8827 latch be used for flush transom doors? Does Von Duprin make a strike for surface vertical rod devices with flush transom applications?
Resolution:
Yes, the Von Duprin model 260U strike is intended for surface vertical rod devices with flush transom applications. There is also a fire rated model called the 260U-F.:
What parts are necessary to add the bottom rod/latch/strike to a 98/9927-LBR/LBR-F (less bottom rod) device?
Resolution:
Following parts are required to add the bottom rod and latch to the 98/9927-LBR/LBR-F device. Bottom Rod: 050515 for 9827 and 050514 for 9927 (specify finish) Bottom Latc...: