electric strike allowed on lead lined door?

RELATED FAQS

Question
Answer
Lead lined frames are intended for use in the X-ray Room locations in Health Care facilities. Frames are provided by Steelcraft prepped as follows:  Frames are supplied knock-down (KD). Fram...
Not specifically for lead lined doors.  But the standard hinges should work and not hit the lead lining in the door.  Since standard lead layers vary, check with door manufacturer an...
Ives does not offer any lead lined pivots.  Some of the Ives pivots can be used on lead lined doors such as the 7230F, 7237F, 7230F/7237F Int.  The hole pattern for the mounting screws are offs...
The door template L1 states: "Lead Lining: When L9000-Series or L400-Series locks are ordered with lead lining, add 1/8" to the width of the mortise cut-out on the lock case cover side of installa...
Radiation, Lead Lined
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
The Von Duprin 5100 electric strike is not for fire rated applications.
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into a standard 4 ...