What could cause the Von Duprin EL solenoid not to hold when mechanism cover plate is slide over the solenoid?
Resolution:
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment. You must lengthen the rod by turning the hex nut in front of the plun...:
What is needed to keep the EL device retracted all day?
Resolution:
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
Are the Falcon EL solenoids rated for continuous duty?
Resolution:
The Falcon EL devices can be operated in a continuous duty cycle.:
EL Device Troubleshooting Guide
Resolution:
VISIT US.ALLEGION.COM/EL-SUPPORT FOR TROUBLESHOOTING VIDEO, DOWNLOADABLE GUIDE, AND INSTALLATION INSTRUCTIONS(For best viewing, use Chrome or Firefox browser.)ALLEGION EL SOLENOID ELECTRI...:
Why is the Von Duprin PS873 power supply buzzing or chattering?
Resolution:
Some transformers in the power supplies provide a little humming noise and that is normal. If the humming in Von Duprin PS873 power supply is loud follow these steps. Remove the load from the outp...: