Question
Answer
How many Von Duprin QEL devices can be connected to a power supply?
Resolution:
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...:
Will the 900-2Q option board operate an EL device?
Resolution:
The 900-2RS is recommended to be used with EL devices but if you have a 900-2Q with PS914 power supply it can be used to operate up to two EL or one EL and one QEL devices .:
Why is my latch not retracting when I depress the push pad on an XP98/99 device?
Resolution:
Pushing on the push bar or activating the EL/QEL or the trim on Von Duprin XP98/99 exit device does not retract the latch, it releases the latch only. Door must be pushed or pulled when device o...:
What are the Von Duprin part numbers for RX, LX and RX,LX-LC switch kits for field installation?
Resolution:
The attached table shows the part numbers for LX-RX and LX-RX-LC switches field installed.:
Is the EL wiring adapter needed for QEL?
Resolution:
The EL wiring adapter is not needed for QEL devices.:
Will the MPB-842 or MPB-840 power EL or QEL devices?
Resolution:
The old MPB842 power supply will power up to two EL electric panic bars but will not power the QEL devices. A defective potted module inside the electric panic bar or defective power supply coul...:
How many times can an EL device be operated when using a PS914-2RS with battery backup?
Resolution:
The Von Duprin PS914-2RS retracts the EL or QEL device approximately 200 times with five second hold time after each pull.: