EL requires which EPT

RELATED FAQS

Question
Answer
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....
For Product Shipped Prior to August 2012 using the old (black) potted module:a.       0-100 ft 14 gauge wireb.      0-200 ft 12 gauge wire&nbs...
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Applies to L9090EL/EU, L9091EL/EU, L9092EL/EU, L9093EL/EU, L9094EL/EU, L9095EL/EUThe Schlage electrified L-Series wiring diagram can be found here and the re...
Applies to L9080EL/EU. L9082EL/EU (Discontinued)The Schlage electrified L-Series wiring diagram can be found here and the requirements are listed below. 24VAC or 24VDC (maximum 26V, ...
Click here to show the differences of an installed lockcase between the L9090, L9091, L9092, L9093, L9094, L9095 EL/EU and the L9080 EL/EU
This option is not available as the solenoid is in the mechanism case where the dogging components would go.  An HD-EL solenoid is not available, and Special Dogging(SD) is not an option ...