EL PULLS AND RELEASE

RELATED FAQS

Question
Answer
(For best viewing, use Chrome or Firefox browser.)ALLEGION EL SOLENOID ELECTRIC LATCH RETRACTION TROUBLESHOOTING GUIDE IF DEVICE LATCH IS NOT RETRACTING PROPERLY WHEN POWERED, FOLLOW THESE STEPS I...
Following could cause the EL device to pull and drop repeatedly.  Short to ground  on EL wiring.  Incorrect wire gauge used.  For wire run and gauge requirements, click HERE  Wrong power suppl...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment.  You must lengthen the rod by turning the hex nut in front of the plun...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...