EL potted modules.

RELATED FAQS

Question
Answer
EL wiring harness is no longer needed with new EL potted modules.
The PS873-2 power supply will still operate the EL with new potted module.
For Potted Modules shipped before August of 2012, you can test by applying power to the potted circuit breaker to and if good the following voltages will be seen: 23-24V DC on the gree...
The power to the Von Duprin potted module also called potted circuit breaker is non polarized.
Following items could cause the DC output on PS914 series power supply to drop when access control is activated. Wrong gauge wire from power supply to the the power transfer. Excessive wire run...
One of the following items may cause the EL1690 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
Following could cause the fuse to blow in Von Duprin PS873 power supply. PS873 power supply provides 2AMP at 24VDC or 4AMP at 12VDC. If this limit is exceeded the fuse will blow in the power sup...