El device retracts only part way

RELATED FAQS

Question
Answer
Followings are the list of the electric latch retraction EL/HDEL (hex dogging), QEL (quiet) kits: 114317-00 QELA Mod. Conv. Kit 040061-00 QELA Mod. Conv. Kit...
The best way to test the Von Duprin EL solenoid is with an ohm meter. You must test both coils to make sure the solenoid is good. The coil has three wires; green, yellow, and orange. The green wire...
 Electric latch retraction, EL, devices are only available in 24VDC.
This is not possible as an EL device is an electric latch retraction and requires power to unlock the door thus only available in Fail Secure.
 HD-EL (Hex Dogging Electric Latch Retraction) solenoid and plunger can be replaced with standard EL solenoid and plunger on non fire rated exit devices, but this should not be used on a daily basi...
 EL devices are wired to the Senior Swing, using the P10 (761465) cable.  Connect the "GRAY" wire to the SC terminal on the 900-2RS card in the Von Duprin Power Supply and the "VIOLET" wire to the ...
EL is Electric latch retraction and retract the latch bolt into the exit device center case.  E references the electric unlocking of the Pull Side trim for a Panic Device.   With the E function, th...
Application is based on how the door will be used.   Please contact Product Support at 877-671-7011 to discuss your application and select the correct device for your opening.
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
The Von Duprin EL option can be added to any existing 33A/35A, 98/99 series exit devices. 
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
  Pushing on the push  bar or activating the EL/QEL or the trim on Von Duprin XP98/99 exit device does not retract the latch, it releases the latch only. Door must be pushed or pulled when device o...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device locks the p...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
There is no conversion kit to add EL or ED to an existing 1690 or 1790 series device. All of the components are built into the device, since the device does not have a separate baseplate.  You ...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
No, Von Duprin exit alarm ALK and electric latch retraction QEL or EL are installed in the same location and can't be ordered together with the same device.
Electric Latch Retraction(ELR) option for the 19 Series was discontinued in December of 2006.
The Falcon EL devices can be operated in a continuous duty cycle.
- AD Series and CO series products require that the Night Latch (NL) screw is installed in the exit device.  Be sure this screw is installed- Exit hardware and strike must be properly mounted ...
EL only retracts the latchbolt or vertical rods/latches. ED retracts the latchbolt or vertical rods/ latches and the push pad of the device at the same time.