drilling specs for AD series lock

RELATED FAQS

Question
Answer
Customers will need to use the Schlage Utility Software (SUS) on the HHD lock programming device to set the desired magnetic track to be read for access control, if not using default Track 2&n...
Order the M204-198 thru-bolt jig, see Figure 1. Figure 1: M204-198 thru bolt jig The 40-080 was the old Schlage jig. The 030736-000-70 was the old Falcon jig.  When the jig changed to...
ALWAYS put the PIM400 in LINK mode first. On a PIM400-TD2 press the LINK1 Button for door one, and LINK2 button for door 2. With a PIM400-485 you must use the SUS/HHD to select which door to LINK.  
1. To put the AD400 in LINK mode, hold down the RTE (Lever or crash bar see below) and press the # key on the key board, or present a card to the reader.            Why press the # key? Because t...
2. AD400 requires a Request To Exit (RTX) signal to link - see the user guide instructions for the linking process.  For an AD400 to enter link mode, it must see the RTX (Request To Exit) switc...
   3. Check the AA battery level, if the AA batteries are below 4.7 volts the AD400 can fail to LINK.             Install fresh batteries, with a level of 6.0 volts or better.  
4. PIM400/AD400 COM400 plug could be damaged! The small pins in the Main PCB board connection for the RF COMM board can get bent during installation of the RF COM400 board. If the PINs are bent a...