DOUBLE DOOR RIM DEVICE WITH STRIKE NO MULLION
”
RELATED FAQS
Question
Answer
What is the backset for a 98/99 rim device with a 1609 strike?
Resolution:
The backset for a 98/99 rim PANIC device with 1609 strike is 2 3/8" from center of the opening to center line of the device. See template :
What strike do I use with a pair of 22 rim device without a mullion?
Resolution:
The 1609 strike can be used on an inactive door with 22 rim device. NON-FIRE RATED doors only. :
What is the minimum door width for a 98/99 Rim device with 4954 mullion?
Resolution:
Minimum door opening for a 98/99 rim device with a 4954 mullion and 299 strike is 26.687" (26 11/16"):
Why does the auto operator not open the door when installed with a Chexit?
Resolution:
Chexits are NOT electric latch retraction devices, therefore the latch will not retract and allow the opener to swing the door open. Chexits block and unblock the latch. In order for a Ch...:
Which strike do you use with an XP98/99 device?
Resolution:
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.: