DOES CX NEEDS FA INTERFACE

RELATED FAQS

Question
Answer
The circuit board is sometimes referred to as a "module" in the field.
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
-         With the CIP NOT inserted and the Schlage Utility Software (SUS) running o   Enter the Master Programming PIN or Present Loc...
Some Access Control Panels are designed with “Supervised” or “Dry contact” requirements for the inputs and have no common ground between the ACP (Access Control Panel) and device at the door. “S...
Schlage offers the “RLBD” to support these supervised or dry contact interface applications. The "RLBD" plugs directly into the PIM400-TD2 or PIB300-TD2 for easy hook-up.  
Please reference this Tehnical Note RLBD SES-20120418 for RLBD setup, use information, hook-up diagrams and some testing suggestions when connecting to a Supervised dry contact Access Contro...
This is a link to the RLBD Installation Instructions.
This RLBD data sheet can also be found at Schlage/Technical Support. RLBD DataSheet
113781 is the part number for Von Duprin 15 second CX sign.