Question
Answer
Can a Von Duprin delay egress controller DE5101 run a pair of doors?
Resolution:
One Delayed Egress Controller (DE5101) can run two mag locks on a pair of doors, provided the doors are not controlled independently:
Is there a Von Duprin delay egress Chexit conversion kit?
Resolution:
There is no conversion kit for Von Duprin Chexit device. If delayed egress Chexit device is required, the entire device must be replaced.:
Schlage M490DE Maglock - Can Delay Egress be Remotely Disabled
Resolution:
No, only via DIP switch 8 and/or the aux input. :
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...: