deadlatch von duprin

RELATED FAQS

Question
Answer
There are two main differences:The bottom latches are differentThe Von Duprin 98/9947 concealed vertical rod device covers up to 1/4" undercutThe Von Duprin 98/9948 concealed vertical rod device co...
They both use Template # 10320_c
To convert the Von Duprin 360L/TL from nightlatch to classroom or from classroom to nightlatch invert mortise cylinder cam.
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts.  This may NOT be used on Fire Rated openings.
LR is the regular/ standard latch and PL is Pullman/ES (Electric Strike) latch for the Von Duprin 8827 exit device.
 ES (electric strike) latch is only used with the 8827 less bottom rod on a non fire rated exit device with a 6111 electric strike.
Von Duprin does not offer any lever trim or pulls that through bolt to the Guard X device.  Ives has the 8102-6 and 8105-6 pulls that can be lined up with the mounting screws of the exit device b...
The LX switch is not available with Von Duprin rim and vertical rod Chexit devices. If using a mortise Chexit device the SS7500 mortise lock would provide a LX latch bolt monito...
We do not offer a true night latch, storeroom or ANSI "03" function with this device. (Entrance by trim when latchbolt is retracted by key. Key removable only when locked.) This function would da...
We do not offer the 230L with night latch function. There is no conversion available.
Followings are the list of the electric latch retraction EL/HDEL (hex dogging), QEL (quiet) kits: 114317-00 QELA Mod. Conv. Kit 040061-00 QELA Mod. Conv. Kit...
The spring in the hinge case or end case assembly lifts the crossbar and both lever arms.  If broken, the crossbar and lever arms will drop down. The weight of the crossbar and levers will automati...