Concealed vertical rod device application electric strike
”
RELATED FAQS
Question
Answer
Can the 283 strike be used with a metal frame with concealed vertical rod devices?
Resolution:
No, per the UL Compliance group, the concealed rod devices are only tested with the 338 strike with metal frames. This applies to panic and fire applications. The 283 strike may only be used ...:
Can the Von Duprin 8827 latch be used for flush transom doors? Does Von Duprin make a strike for surface vertical rod devices with flush transom applications?
Resolution:
Yes, the Von Duprin model 260U strike is intended for surface vertical rod devices with flush transom applications. There is also a fire rated model called the 260U-F.:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
Is the Von Duprin 1609 strike fire rated for pairs of doors?
Resolution:
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...:
Where is the template for the 718 trims made after 2/28/2011 for Falcon/Monarch concealed vertical rod devices?
Resolution:
Templates for current 718 series trim can also be found on Falcon website:
Can I use an AD or CO - 993 Exit Trim with a Von Duprin 98/99 Concealed Vertical Rod exit device on a wood door?
Resolution:
The AD or CO - 993 is NOT compatible with a Von Duprin 98/99 Concealed Vertical Rod exit device on wood doors.: