chexit latch re-arm
”
RELATED FAQS
Question
Answer
Will CX re-arm if door is held open?
Resolution:
If a door position switch (DPS) is connected across the green and white wires of the old CX (green and red of new CX) the CX would go into alarm if the door is held open when it attempts to rearm.&...:
Chexit goes into alarm with fast flashing LED and not locking after rearm time.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...:
Can Von Duprin QEL/EL and CX be in the same device?
Resolution:
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device ...:
Solenoid on Chexit pulls back and immediately lets go and alarm goes off with red solid light.
Resolution:
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...:
CX will not arm. Red light on solid waits 10 sec, light goes out and cycle repeats
Resolution:
Inadequate power or wrong gauge wire is used. The inrush current demand by CX will overload and shutdown the power supply if undersized. You must use the Von Duprin PS873 or...:
Will a 4040SE open and hold at 180°?
Resolution:
No, LCN does not have an electronic hold open closer (SE/ME Series) that will provide a solid 180° hold open position. The 3130SE has an adjustable hold open position from 85° to 110° maximum. ...: